themra bridge detail   
 

Calculation method for assessing Thermal Bridging at the edges of openings

Example
The adjacent diagram shows a window jamb in a masonry cavity wall, with Therma-Bridge Plus closing the cavity.

Robust details require a cavity closer with a minimum Thermal Resistance path of 0.45m:²K/W.

Calculaion of Thermal Resistance Path (‘R’ value)
This table shows the thermal resistance for each segment of the path ABCDE. The thermal resistance for each segment is obtained by dividing the length of the path segment in metres by its thermal conductivity in W/mK

Path Segments
Length (m)
Conductivity
(W/mK)
Resistance
(m:²K/W)
A-B
0.0275
0.12
0.23
B-C
0.015
1.13
0.013
C-D
0.018
0.038
0.474
D-E
0.04
0.770
0.052
Thermal Resistance Path (‘R’ value) = 0.769m:²K/W

 

 

 
 
Elimiates Cold Bridging Fully Certified
1,000,000 + m/Linear Supplied CFC/HCFC Free
Rigid Lengths Ease Installation Meets NHBC and Robust Standards
 