Calculation method for assessing
Thermal Bridging at the edges of openings

Example
The diagram below shows a window jamb in a masonry cavity wall, with Therma-Close closing the cavity.
Robust details require a cavity closer with a minimum Thermal Resistance of 0.45m²K/W

Calculation of Thermal Resistance Path (‘R’ value)
This table shows the thermal resistance for each segment of the path ABCD. The thermal resistance for each segment is obtained by dividing the length of the path segment in metres by its thermal conductivity in W/mK

Path segments Length (m) Conductivity (W/mK) Resistance (m²K/W)
A - B
0.0275
0.12
0.23
B - C
0.030
0.029
1.034
C - D
0.040
0.770
0.052
Thermal Resistance Path ('R' value) = 1.316m²K/W



 
 